PVC-Leitungsdraht, Steuer- und Versorgungsleitung JZ-500 BLACK 12G1,5 mm² schwarz, Adern schwarz nummeriert nach DIN VDE 0293-334 10369
Empfohlene Produkte
TECHNISCHE DATEN
Maße und Gewicht bezogen auf die Verkaufseinheit: 1 M
PVC-Leitungsdraht, Steuer- und Versorgungsleitung JZ-500 BLACK 12G1,5 mm² schwarz, Adern schwarz nummeriert nach DIN VDE 0293-334 10369
Flexible control cable JZ-500 – reliability and durability in every application
This 12-core JZ-500 cable with a cross-section of 1.5 mm² is a versatile solution for medium-load electrical installations. The cable is characterized by high flexibility, making it ideal for connections requiring frequent bending and movement. Made from high-quality materials, it ensures safe and long-lasting operation in a variety of conditions.
Construction and properties
The JZ-500 cable has been designed for demanding applications. Its construction includes:
- Copper conductors: Multi-strand, flexible copper conductors of class 5 provide good conductivity and resistance to material fatigue.
- PVC insulation: Each core is insulated with special PVC (Z 7225), guaranteeing high electrical and mechanical resistance.
- Core marking: Black cores with white numbers facilitate identification and connection, minimizing the risk of errors during installation. Additionally, a yellow-green protective core is present for increased safety.
- Outer PVC jacket: A durable outer jacket made of special PVC (TM2) provides protection against mechanical damage, weathering, and the influence of oils and chemicals. The jacket color is black (RAL 9005).
- Metering: The cable is supplied in meter lengths, making it easy to precisely adapt to installation needs.
This cable also stands out for its UV resistance and self-extinguishing properties, confirmed by tests in accordance with DIN VDE 0482-332-1-2 and DIN EN 60332-1-2/IEC 60332-1. The materials used in production are free of silicone, cadmium and substances that interfere with painting.
Applications and operating parameters
The JZ-500 cable is used in a wide range of electrical installations:
- Mechanical industry: Control, signaling and measurements in production lines and conveyor belts.
- Indoor installations: Laying in dry, damp and wet rooms.
- Outdoor installations: Can be laid in the open air (avoid direct burial in the ground or laying under water).
Cable operating parameters:
- Rated voltage: 500 V
- Operating temperature range (flexible): -15°C to +80°C
- Operating temperature range (stationary): -40°C to +80°C
- Minimum bending radius (flexible): 7.5 x cable outer diameter
- Minimum bending radius (stationary): 4 x cable outer diameter
- Outer diameter: approx. 13.2 mm
The cable meets the requirements of the Low Voltage Directive 2014/35/EU (CE marking) and has a fire reaction class Eca according to CPR standard. It complies with DIN VDE 0285-525-2-51/DIN EN 50525-2-51 standards.
ZERTIFIKATE, ZULASSUNGEN, SICHERHEIT, KONFORMITÄT UND WARNHINWEISE
Konformitätsbescheinigung
Anhänge