Disjoncteur S 311 1P B 25A 10000A TX3 404086

depuis 1 pièces39,31 zł
brut / pièces
livraison 5 jours
z 2 pièces
z 2 pièces
Marque LEGRAND
Série:S31TX
Index d'Onninen:HEC558
Index des fabricants:
404086

Numéros de catalogue :

  • 006702
EAN:
3414970391896
  • 3245060067021
Emballage en vrac:1 / 10 / 3000 pièces


PRODUITS SUGGÉRÉS


DONNÉES TECHNIQUES

Dimensions et poids de l'unité de vente: 1 pièces

longueur/largeur/haut/Balance/objet:0,184 m / 0,1 m / 0,088 m / 1,381 kg / 0,002 m3
Code douanier:85362090

Disjoncteur S 311 1P B 25A 10000A TX3 404086

Protection of single-phase circuits in residential and commercial installations

The S 311 circuit breaker from the TX³ series is a single-pole device designed to protect against the effects of short circuits and overloads in single-phase circuits. It features a rated short-circuit capacity of 10 kA according to EN 60898-1 and 16 kA according to IEC 60947-2, making it suitable for both standard residential installations and commercial facilities with higher requirements.

A rated current of 25 A combined with B characteristic means that the electromagnetic trip will act at loads exceeding 3-5 times the rated value. This feature makes the breaker perform well in circuits with small electric motors and devices with low inrush current - where higher characteristics (C or D) might react too slowly or cause unnecessary tripping.

The width of one module on a TH35 rail allows for compact mounting in distribution boards where available space is limited. The design with bottom terminals and covers simplifies wiring - wires are inserted effortlessly, and the risk of accidental contact with live parts is minimized.

Operating parameters and environmental conditions

The device operates on a 230/400 V AC network at a frequency of 50-60 Hz. The maximum operating voltage reaches 440 V AC, providing a safety margin in typical installation conditions. An insulation voltage of 500 V and an impulse withstand voltage of 4 kV confirm the device's resistance to surges occurring in building installations.

The IP20 protection rating means the breaker is protected against finger contact and access to live parts, but it is not intended for damp rooms - where enclosures with a higher IP class should be used.

A mechanical durability of 20 000 operations and electrical durability of 10 000 operations attest to the robustness of the construction and readiness for many years of operation. Energy limiting class 3 indicates effective damping of short-circuit energy - the trip quickly interrupts the electric arc, protecting both the device itself and other elements of the installation.

Compatibility and expansion

TX³ series breakers work with a wide range of auxiliary accessories - auxiliary and signaling contacts, undervoltage and shunt trips, as well as remote switching actuators. This allows for the construction of advanced systems for signaling device status or automatic control of the distribution board.

The connection of wires with cross-sections from 1 to 25 mm² enables the use of both thinner control wires and thicker power cables without the need for adapters. The breaker is mounted on a standard TH35 rail - the same way as most modular devices available on the market.

The black switching lever ensures a clear device status even in poorly lit distribution boards. The grey housing (RAL 7035) maintains visual consistency with other elements of the TX³ series.

The breaker complies with IEC/EN 60898-1 and IEC/EN 60947-2 standards - it can be used as standalone protection or work in conjunction with separately mounted residual current devices (the breaker itself does not support RCD connection).


CERTIFICATS, APPROBATIONS, SÉCURITÉ, CONFORMITÉ ET AVERTISSEMENTS

Déclaration de conformité

Informations sur les pages www

Pièces jointes



PRODUITS SIMILAIRES / AUTRES TAILLES


depuis 1 pièces39,31 zł
brut / pièces
livraison 5 jours
z 2 pièces
z 2 pièces