Overhead earth disconnect switch RUNMp III SA 24/4 03-020
Suggested products
TECHNICAL DATA
Sales unit dimensions and weight: 1 pcs
Overhead earth disconnect switch RUNMp III SA 24/4 03-020
Air disconnect-earthing switch – a reliable protection for medium voltage lines
The RUNMp III SA 24/4 disconnect-earthing switch is a key element of energy infrastructure, designed for the safe disconnection and grounding of circuits in overhead medium voltage lines. This device, manufactured by ALPAR, combines the functions of a disconnector and an earthing switch, providing comprehensive protection for the installation. The modular design allows for vertical mounting, which facilitates integration with existing pole infrastructure.
Construction and application
The RUNMp III SA 24/4 is characterized by a three-pole design based on a common frame and a drive for all poles. Each pole is built on two support insulators – one attached to the base, the other to the movable bearing beam. This solution ensures simultaneous closing and opening of all poles, which is important for maintaining network continuity. The current path of each pole consists of main and auxiliary (mig) contacts, mounted on support cassettes directly on the insulators. This allows for effective switching of electrical circuits and safe grounding of disconnected parts of the installation.
Advantages and benefits
High reliability: The design based on proven solutions and high-quality materials guarantees long-term and trouble-free operation of the device.
Versatility: Vertical mounting allows for easy adaptation to different pole and power line configurations.
Safety: The grounding function provides effective protection against accidental re-energization of the circuit during maintenance or repair work.
Durability: Hot-dip galvanizing of steel elements provides excellent anti-corrosion protection, extending the life of the device even in harsh weather conditions.
Connection flexibility: The flexible contact in the version with grounding minimizes the risk of damage to wires during operation.
Compliance with standards: The disconnector meets the requirements of PN-EN 62271-103 and PN-EN 61140, confirming its safety and quality.
Easy installation and adjustment: The simple design allows for quick and efficient installation and adjustment of the device on site.
Operating parameters and compliance with standards
The device is designed to operate in overhead lines with a rated voltage of 24 kV and a rated continuous current of 400 A. It withstands a short-circuit current of up to 16 kA and a peak current of up to 40 kA for a short-circuit duration of 1 second. It meets the requirements of PN-EN 62271-103 and PN-EN 61140 regarding the safety and technical parameters of high-voltage switchgear. It is designed to operate at temperatures from -40°C to +40°C and air humidity below 100%.