Construction distribution board TD-S 16A 2x230V Mennekes Doktorvolt 6961 sockets DV-6961-F
Suggested products
TECHNICAL DATA
Sales unit dimensions and weight: 1 pcs
Construction distribution board TD-S 16A 2x230V Mennekes Doktorvolt 6961 sockets DV-6961-F
Ready-made solution for power supply on construction sites and in the field
The TD-S construction distribution board is a complete power station enclosed in a compact surface-mounted housing with dimensions 360 × 250 × 185 mm. It is equipped with two single-phase sockets 230 V / 16 A (French system with grounding pin) and one industrial socket 400 V / 16 A - all in IP44 rating, allowing for safe outdoor operation even in precipitation or dusty environments.
The housing is made of technopolymer, the door of polycarbonate, and the seal of EPDM rubber - a combination of materials resistant to impact and weather conditions. The front plate is grey RAL 7035, and the rear is black. Stainless steel mounting screws and the included PG-16 cable gland facilitate on-site installation.
Protection and internal switchgear
Each socket has its own overcurrent protection - C16 circuit breakers with a breaking capacity of 10 kA. Two single-pole breakers protect the 230 V sockets, and one three-pole breaker protects the industrial socket. The 3F + N + PE /12 mm² busbar ensures proper connections between the components and the power supply.
Industrial and single-phase sockets
The industrial socket in a red housing is an industrial product, Type 1385, five-pole (3P + N + PE), designed to power heavy-duty equipment. The single-phase sockets operate in the French type (Type E) system with a central grounding pin - a popular standard for construction power tools.
Compliance with standards and certificates
The housing meets CE, CEI-23-48/49, and IEC 670 requirements. The circuit breakers are certified according to the EN60898 and EN60947-2 series standards, confirmed by EFS, EFC, and VDE markings. The manufacturer has implemented a quality management system certified by TÜV SÜD according to ISO 9001:2015.
The total rated current is 48 A, with an operating voltage of 230/400 V /50 Hz AC. An RDF coefficient of 0.9 indicates the permissible continuous load under standard temperature conditions.
The distribution board is delivered ready for connection - simply run the supply cables through the PG-16 gland to the main distribution board or construction panel.
CERTIFICATES, APPROVALS, SAFETY, COMPLIANCE AND WARNINGS
Declaration of Conformity