Module 6000/CCO 73.PM0.02
Suggested products
TECHNICAL DATA
Sales unit dimensions and weight: 1 pcs
Module 6000/CCO 73.PM0.02
Fire alarm system output module
This module, catalog number 73.PM0.02, is a key element for expanding and configuring fire alarm systems from the 6000 series. It is used to control external devices such as acoustic and optical signals, smoke extraction systems, or fire doors. Its main function is to transmit alarm signals from the control panel to connected receivers.
Configuration and flexibility
The 6000/CCO module stands out for its full configurability from the control panel, allowing its operation to be adapted to the specific needs of the installation. Thanks to a relay with switchable NO/NC (normally open/normally closed) contacts, it can be used in a variety of applications – from simply turning devices on/off to more advanced control scenarios. Power supply from the monitoring loop ensures reliable operation and system integrity.
Technical specifications and application
The module is characterized by its compact dimensions (45.5 x 41 x 82 mm) and light weight (0.05 kg), making it easy to install in limited space. The alarm current is 19 mA, and the monitoring current is 0.6 mA. The relay output allows controlling loads up to 1 A / 24 V DC. This makes the module ideal for both installers looking for a reliable component to expand fire alarm systems and end-users expecting a flexible solution for controlling safety devices. The ability to configure through the control panel simplifies the integration process with existing infrastructure and allows for quick adaptation to changing requirements.