Module 6000/2LPZA 73.PM0.09

from 1 pcs1 198,64 zł
gross / pcs
to order
Brand PROTEC
Onninen Index:CKZ362
Manufacturer's code:
73.PM0.09

Catalog numbers:

  • PR00075
Bulk packaging:1 pcs


Suggested products


TECHNICAL DATA

Sales unit dimensions and weight: 1 pcs

length/width/height/weight/volume:0,1465 m / 0,042 m / 0,118 m / 0,2 kg / 0,001 m3
Customs code:85311030

Module 6000/2LPZA 73.PM0.09

Side Lines and Indicator Module – Fire Alarm System Expansion

This module, catalog number 73.PM0.09, is a key element in expanding fire alarm systems with additional detection and signaling lines. Designed to work with series 6000 control panels, it allows connection of two conventional detection lines and two conventional indicator lines. This solution is ideal for both professional installers and end-users looking for a reliable and flexible fire protection system.

Functionality and application

The 6000/2LPZA module is powered directly from the monitoring loop, simplifying installation and ensuring continuous system operation. This eliminates the need for additional power supply, and its operation is an integral part of the main alarm system. It finds application in facilities requiring an extended detection and fire signaling network, such as:

  • Public buildings (schools, hospitals, offices)
  • Industrial and warehouse facilities
  • Hotels and multi-family residential buildings
  • Installations where independent control of several fire zones is required

Technical characteristics and benefits

The module is characterized by compact dimensions (146.5 x 42 x 118 mm) and low weight (0.20 kg), making it easy to install even in hard-to-reach places. The applied technical solutions ensure high reliability and resistance to interference. It is worth paying attention to several key parameters:

  • Input voltage: 18 – 28 V DC – compatibility with most standard alarm systems.
  • Alarm current: 15 mA – ensures quick and effective activation of indicators.
  • Supervision current: 1.6 mA – minimizes energy consumption in standby mode.
  • EOL inputs: 8.2 kΩ – allow monitoring the status of detection lines for damage or sabotage.
  • EOL outputs: 10 kΩ – ensure monitoring of the status of signaling lines.
  • Maximum load of signal lines: 50 mA – allows connection of various acoustic and optical indicators.

Thanks to this, the module not only expands the capabilities of the fire alarm system, but also increases its safety and effectiveness. The module design takes into account the possibility of using ROP resistors with a value of 330 Ω or 180 Ω, providing flexibility in the selection of installation elements.

Type
Conventional sidelines
Input voltage
18… 28 V DC
Current in alarm
15 mA
Current in supervision
1.6 mA
Number of entrances
2
Entrances
8.2 kOhm EOL
max. current at rest 500 μA
MCP with 330 Ω or 180 Ω resistor
Number of outputs
2
Exits
EOL 10 kΩ
load on signal line 50 mA
W x H x D
146.5 x 42 x 118 mm
Libra
0.20 kg

CERTIFICATES, APPROVALS, SAFETY, COMPLIANCE AND WARNINGS