Fire-resistant cable HDGSEkwfżo FE180/PH120/E90 3x1.5 B52251

from 100 m19,52 zł
gross / m
to order
Onninen Index:CRH200
Manufacturer's code:B52251
EAN:5902956643094
Bulk packaging:100 m


Suggested products


TECHNICAL DATA

Sales unit dimensions and weight: 1 m

length/width/height/weight:1 m / 0,0083 m / 0,0083 m / 0,099 kg
Customs code:85444995

Fire-resistant cable HDGSEkwfżo FE180/PH120/E90 3x1.5 B52251

Fire-resistant power cable – safety and reliability of installation

This fire-resistant, halogen-free power cable is designed to operate in installations requiring continuous power supply during a fire. This cable is used in fire protection systems, emergency lighting, smoke extraction systems, and other critical applications where reliable operation is key. The use of silicone rubber as insulation for the cores ensures high thermal and chemical resistance.

Construction and properties

The cable is characterized by a construction that provides high resistance to fire and temperature. Made of solid copper conductors, it has insulation made of cross-linked silicone rubber (LSZH), which guarantees the absence of toxic gas emissions during combustion. The twisted core is wrapped with polyester and mica tape, which further increases its mechanical and thermal strength. Thanks to this, the cable meets strict fire safety standards.

The HDGSEkwfżo FE180/PH120/E90 cable is distinguished by maintaining the PH120 function and FE180 insulation resistance, which means the ability to maintain continuous operation for a specified time under fire conditions. It has a reaction to fire class of B2ca-s1a, d0, a1 according to PN-EN 13501-6, which confirms its high fire resistance properties and low flammability.

  • Halogen-free coating: Ensures safety for people and equipment in the event of a fire by eliminating the emission of toxic gases.
  • Temperature resistance: The cable retains its properties over a wide range of operating temperatures from -30°C to +80°C, and can withstand short-term loads up to +250°C in the event of a short circuit.
  • Application in sprinkler zones: Possibility of laying inside buildings, also in zones equipped with water sprinklers (according to PN-EN 50200).
  • Low smoke emission: Limits the spread of smoke during a fire, improving visibility and facilitating evacuation.
  • Copper conductors: Ensure good electrical conductivity and a reliable connection.

This cable is ideal for both professional installers carrying out fire protection projects and end customers looking for safe and reliable solutions for their electrical installations. Its use guarantees the protection of life and property in emergency situations.


CERTIFICATES, APPROVALS, SAFETY, COMPLIANCE AND WARNINGS

The declaration of performance