Overcurrent circuit breaker ETIMAT 10 2P C2 002133708

from 1 pcs103,18 zł
gross / pcs
delivery 5 days
z 23 pcs
z 23 pcs
Brand ETI
Series:ETIMAT
Onninen Index:CQC271
Manufacturer's code:002133708
EAN:3838895260028
Bulk packaging:1 / 6 / 54 pcs


Suggested products


TECHNICAL DATA

Sales unit dimensions and weight: 1 pcs

length/width/height/weight:0,054 m / 0,0908 m / 0,0766 m / 0,229 kg
Customs code:85362010

Overcurrent circuit breaker ETIMAT 10 2P C2 002133708

Reliable protection of electrical installations

ETIMAT 10 circuit breaker is a key element of every electrical installation, providing effective protection against the effects of overloads and short circuits. Designed for use in residential buildings, public facilities, and industry, it guarantees safety and reliable operation. The design and parameters of this circuit breaker have been designed for easy installation and long-term operation.

Functionality and technical parameters

The ETIMAT 10 circuit breaker is characterized by a rated current of 2A and a C characteristic, which means that it reacts with a delay to short-term current surges – an ideal solution for circuits with devices with high starting current, such as motors. The rated short-circuit breaking capacity of 10 kA at 230 V and 400 V (according to EN 60898) and 15 kA at 230 V and 15 kA at 400 V (according to IEC 60947-2) ensures a quick and effective response in emergency situations. A width of 2 modules allows for optimal use of space in the switchgear cabinet.

  • C characteristic: Provides a delayed response to short-term overloads, protecting against unnecessary tripping of the circuit.
  • Short-circuit breaking capacity: High rated values guarantee effective protection of the installation in the event of a short circuit.
  • Mounting: Easy mounting on TH35 rail – a standard solution that facilitates installation.
  • Wire cross-section: Possibility of connecting solid and stranded wires with a cross-section from 1 to 25 mm², which provides flexibility during installation.
  • Operating temperature: A wide range of operating temperatures (-25°C to +55°C) allows the circuit breaker to be used in various environmental conditions.

Additional features and compliance with standards

The ETIMAT 10 circuit breaker meets the requirements of IEC/EN 60898-1 and IEC 60947-2 standards, which confirms its high quality and safety of use. It has energy limitation class 3 and surge category III, which makes it suitable for use in most typical electrical installations. The degree of protection IP20 provides protection against accidental contact and against the ingress of solid objects larger than 12.5 mm. Additionally, the possibility of mounting auxiliary contacts and an overcurrent release increases the functionality of the device, allowing it to be adapted to the specific needs of a given installation.