Circuit breakers ETIMAT 10 are reliable and proven solutions designed to protect electrical installations in residential buildings, public facilities, and industry. They provide effective protection against the effects of short circuits and overloads, guaranteeing safe operation. The design and parameters of these circuit breakers make them suitable for both professional installers and end-users looking for solid protection for their installations.
Characteristics and application
ETIMAT 10 circuit breakers are characterized by a rated current of 100A and a D tripping characteristic, which means they are ideal for protecting circuits with receivers with high inrush current – for example, motors. The rated short-circuit breaking capacity (Icu) is 15kA at 230V and 15kA at 400V, which ensures an effective response in the event of a failure. A width of 4.5 modules allows for efficient use of space in the distribution board. Made of high-quality materials, they ensure durability and reliable operation for a long time.
Construction and mounting
ETIMAT 10 circuit breakers are designed for easy mounting on a TH35 rail. The possibility of connecting wires with a cross-section from 2.5 mm² to 50 mm² (solid or stranded) provides flexibility during installation. Additionally, these circuit breakers offer the possibility of power supply from the top and bottom, as well as a double connection of the pin-type insulating busbar – top and bottom – which facilitates adaptation to specific mounting conditions. The contact position indicator allows for quick visual control of the circuit breaker status, and the ability to seal the lever in the "On" and "Off" positions increases safety.
Compliance with standards and additional parameters
ETIMAT 10 circuit breakers meet the requirements of IEC/EN 60898-1 and IEC 60947-2 standards, which confirms their compliance with European safety standards. They operate in an ambient temperature range from -25°C to +55°C, which allows their use in various environmental conditions. The rated insulation voltage Ui is 440V and the rated impulse withstand voltage Uimp is 4kV. The IP20 degree of protection provides basic protection against contact and ingress of solid objects.
CERTIFICATES, APPROVALS, SAFETY, COMPLIANCE AND WARNINGS