Measurement alarm module MDP-4.Z/M 4 measurement inputs, 230V power supply with internal battery backup, RS-485 port, 2 outputs for valve
Suggested products
TECHNICAL DATA
Sales unit dimensions and weight: 1 pcs
Measurement alarm module MDP-4.Z/M 4 measurement inputs, 230V power supply with internal battery backup, RS-485 port, 2 outputs for valve
Gas installation safety monitoring module – reliable control
This monitoring module, designed to work with GAZEX gas detectors, is a key element of the detection and protection system in gas installations. The MDP-4.Z/M device provides continuous control and power to up to four detectors, offering comprehensive protection against leaks and hazards. The module is compatible with both measurement and threshold detectors, making it a versatile solution for various types of installations.
Functionality and application
The MDP-4.Z/M module is used in the Two-Threshold Gas Detection System and in the Active Gas Installation Safety System GX. It allows monitoring the status of gas detectors of the type DEX/P, DG/P, DEX/F, DEX/A, DG/F and DG.EN. This makes it possible to quickly detect dangerous gas concentrations and activate appropriate alarm procedures. The module can control additional optical and acoustic signaling devices and cooperate with other devices via relay outputs and the RS-485 port. The version with the "Z" designation allows controlling shut-off valves, providing an additional level of safety.
Key product features
- Versatile compatibility: Cooperation with GAZEX measurement (4-20mA) and threshold detectors, as well as detectors with a relay output (using K-8P/K-16P concentrators).
- Detector status control: Monitoring the current drawn by the detectors and the status of the wired connection – automatic power disconnection in case of failure, without affecting the remaining devices.
- Configurable alarm levels: Possibility of setting two alarm levels for measurement detectors and two for threshold detectors, as well as a fixed threshold for exceeding the measurement range.
- Advanced functions: Calculating the weighted average NDS and NDSCh for toxic gases, the ability to select measurement units (% ,% DGW, mA, ppm) and assigning detectors to zones (S1/S2) for independent control of external devices.
- Operating modes: “QUIET OPERATION” (siren silencing), “SERVICE MODE” (deactivation of outputs) and “AUTO RESET” (automatic resetting of memory states).
- RS-485 communication: Enables integration with building management systems (MODBUS RTU) and data visualization using MD16 View software.
- Built-in protections: Emergency output signaling module or line connection failures.
- Reliability: 230V power supply with internal battery backup guarantees continuous operation even in the event of a mains power failure.
Construction and mounting
The MDP-4.Z/M module is characterized by a solid construction and ease of mounting thanks to removable, self-tightening wire connectors. The device is designed to operate in standard environmental conditions and meets applicable safety standards. The internal memory of the module stores the last 1600 events with information about the start and end time and the source of the event, which facilitates the analysis of potential problems in the future.
CERTIFICATES, APPROVALS, SAFETY, COMPLIANCE AND WARNINGS