Measurement alarm module MDP-4.ZA24/M 4 measurement inputs, 24V power supply, RS-485 port, 2 outputs to valve
Suggested products
TECHNICAL DATA
Sales unit dimensions and weight: 1 pcs
Measurement alarm module MDP-4.ZA24/M 4 measurement inputs, 24V power supply, RS-485 port, 2 outputs to valve
Alarm and measurement module – comprehensive protection and control of gas installations
The MDP-4.ZA24/M measurement alarm module is an advanced device designed to monitor and power gas detectors, both measurement (DEX/P, DG/P type) and threshold (DEX/F, DEX/A, DG/F, DG.EN). It finds application in gas detection systems and active gas installation safety systems, providing reliable protection and a quick response in the event of a hazard. The module allows connection of up to four detectors, offering flexibility in system configuration.
Functionality and capabilities
MDP-4.ZA24/M not only monitors the status of detectors but also provides advanced control and communication functions. Equipped with an RS-485 port, it enables integration with other building management systems (BMS) or data visualization on a PC using dedicated “MD16 View” software. Two outputs to the shut-off valve allow for quick and effective gas shut-off in the event of a hazard. Additionally, the module offers:
- Versatile compatibility: Cooperation with GAZEX detectors with 4-20mA output and threshold detectors with a contact output (using K-8P/K-16P concentrators).
- Detector status control: Monitoring the current drawn by the detectors and the status of the wired connection – automatic disconnection of the power supply to a faulty detector without affecting the others.
- Configurable alarm thresholds: Setting two alarm thresholds for measurement detectors and two for threshold detectors, as well as a fixed threshold for exceeding the measurement range.
- Advanced calculations: Calculating the weighted average of NDS and NDSCh for toxic gases.
- Flexible measurement units: Selection of displayed units: [%] range, [%LEL], [mA] or [ppm].
- Zoning: Assigning detectors to two zones (S1/S2) to control different devices depending on the alarm location.
- Operating modes: “QUIET OPERATION”, “SERVICE MODE”, “AUTO RESET” increase user comfort and facilitate system servicing.
- Alarm signaling: Displaying messages on the LCD, LED signaling and an acoustic siren.
- Event logging: Internal memory storing the last 1600 events with time and source.
Construction and mounting
The MDP-4.ZA24/M module is characterized by a solid construction and easy mounting thanks to removable, self-tightening connectors. This ensures quick system start-up as well as easy maintenance and component replacement. The device is powered by 24V DC, which ensures stable operation in various installation conditions. Additionally, the module has short-circuit and overcurrent protection, which increases its reliability and safety. The manufacturer's warranty is 36 months, confirming the high quality of the product.
CERTIFICATES, APPROVALS, SAFETY, COMPLIANCE AND WARNINGS
Declaration of Conformity
Attachments