Installation cable FLAMEBLOCKER 750 DCA HDXp 2x1.5 RE G-141928

5/5

reviews: 1

from 100 m4,10 zł
gross / m
from 300 m4,00 zł
gross / m
z 5100 m
z 5100 m
Onninen Index:CIV054
Manufacturer's code:G-141928
Bulk packaging:100 / 8400 m


Suggested products


TECHNICAL DATA

Sales unit dimensions and weight: 1 m

length/width/height/weight:1 m / 0,0075 m / 0,005 m / 0,06 kg
Customs code:85444995

Installation cable FLAMEBLOCKER 750 DCA HDXp 2x1.5 RE G-141928

Product features

  • Increased fire resistance installation cable

FLAMEBLOCKER 750 DCA HDXp 2x1.5 RE cable is a reliable solution for electrical installations, especially where high fire resistance and halogen-free properties are required. Designed by TELEFONIKA, this flat installation cable is ideal for use in buildings with stricter fire regulations. Its construction ensures safety and long-term operation.

Construction and application

This cable is characterized by cross-linked polyethylene (XLPE) insulation and an outer sheath of polyolefin – materials guaranteeing high flexibility and resistance to mechanical damage. This makes it suitable for installation in both dry and humid rooms, both under plaster, in walls, and in concrete. Additionally, it has UV protection, which allows it to be used outdoors as well. A separating strand facilitates quick and safe access to the cores without the need for specialized tools.

  • Fire reaction class Dca: Provides a limited contribution to fire development in accordance with EN 13501-6.
  • Halogen-free: Meets the requirements of IEC 60754-1 and IEC 60754-2, which minimizes the emission of toxic gases during a fire.
  • Low smoke emission: Compliance with IEC 61034-2 ensures better visibility during evacuation.
  • Flame retardant: The cable meets IEC 60332-1-2 standard confirming its resistance to flame propagation.
  • Copper cores: Provide excellent electrical conductivity and reliable connections.
  • Core cross-section 1.5 mm²: Optimal for most standard electrical installations.
  • Rated voltage 750 V: Enables use in a wide range of applications.

Parameters for professionals

This cable is also distinguished by a number of technical parameters important for installers: core resistance is 12.1 Ohm/km, and the minimum bending radius in fixed installations is 44.24 mm. The maximum operating temperature of the core is 90°C, and the permissible ambient temperature during installation is -15…50°C. The weight of the cable is approximately 64 kg/km – important information when calculating the costs of transporting and installing large quantities of material. Additionally, the cable has core color marking according to HD 308 S2, which facilitates identification during installation.

Cable insulations tested according to the BS 6724 methodology for a voltage of 3500 V, corresponding to the operation of a cable for a voltage of 1 kV. RIPCORD bursting bundle, wire marking Żo.