Cable HTKSH FE180/PH120/E90 1x2x0.8 B10900
reviews: 3
Catalog numbers:
- 0623 007 23
Suggested products
TECHNICAL DATA
Sales unit dimensions and weight: 1 m
Cable HTKSH FE180/PH120/E90 1x2x0.8 B10900
HTKSH FE180/PH120/E90 Cable – Fire-resistant cable for safety systems
This telecommunication cable, manufactured by Zakłady Kablowe BITNER, is designed for use in installations requiring a high level of fire safety. The HTKSH FE180/PH120/E90 cable is particularly recommended for alarm systems, signaling systems, teletransmission systems, and voice alarm systems (DSO). It will also be suitable for fire automation installations and fire detection systems.
The cable is characterized by high fire resistance – it ensures proper functioning of the installation for up to 120 minutes (PH120) in fire conditions, and its insulation maintains durability for 180 minutes (FE180). Additionally, during combustion, it does not release toxic gases or dense smoke, which increases user safety. The cable is intended for permanent installation inside buildings.
Construction and application
The HTKSH cable has a 1x2x0.8 mm² construction, which means one pair of conductors with a cross-section of 0.8 mm². Thanks to this, it is suitable for transmitting analog and digital signals in industrial electronics and automation installations. It can be used in E90 cable routes as part of an E90 cable assembly, provided it is mounted on dedicated brackets every 30 or 60 cm. The use of CELO brand brackets is particularly recommended.
Key features and benefits
- Fire resistance: FE180/PH120 class guarantees the functionality of the installation during a fire.
- Halogen-free: The absence of toxic gas emissions increases safety in the event of a fire.
- Wide application: Ideal for alarm systems, DSO, fire automation, and other safety installations.
- Durability: High-quality workmanship ensures long-lasting and reliable operation.
- Conductor cross-section: 0.8 mm² allows for efficient signal transmission in various applications.
- Compliance with standards: The cables have been tested in accordance with the requirements of DIN 4102 part 12.
- Insulation resistance: Minimum 500 MΩ/km ensures good electrical insulation.
- Capacitance: 120 nF/km affects the transmission properties of the cable.
- Operating temperature: A range of -30°C to +80°C enables operation in various environmental conditions.