Fire-resistant power cable FLAME-X 950 (N)HXH-J FE180/E90 3x6 RE 1kV G-144664
Catalog numbers:
- G-107454M
Suggested products
TECHNICAL DATA
Sales unit dimensions and weight: 1 m
Fire-resistant power cable FLAME-X 950 (N)HXH-J FE180/E90 3x6 RE 1kV G-144664
Fire-resistant safety cables for demanding applications. The FLAME-X 950 (N)HXH-J FE180/E90 power cable is an advanced solution designed for installations where maintaining power continuity in the event of a fire is critical. Designed to protect people and property, this cable ensures the reliable operation of safety systems such as fire alarms, emergency lighting, and ventilation systems. Its construction based on halogen-free materials minimizes the emission of toxic gases during combustion, further increasing safety.
Construction and properties
The FLAME-X 950 cable is characterized by a solid construction, providing high mechanical and thermal resistance. Copper conductors, available in class 1 (solid core) or 2 (stranded multi-core), are insulated with a special cross-linked halogen-free compound. An additional filling layer and an outer polyethylene coating provide protection against external factors and damage. The orange cable jacket makes it easy to identify in the installation. A version with a protective conductor (N)HXH-J and without it (N)HXH-O is available.
This cable meets stringent safety standards, including DIN VDE 0266, DIN 4102-12 and CNBOP-PIB-KOT-2021/0266-3701 issue 3. It has CNBOP and VDE certificates, confirming its high quality and compliance with applicable regulations.
Application and benefits
This cable is used in a wide range of building and industrial facilities where high fire resistance and minimal emission of toxic substances in the event of a fire are required:
- Public buildings: hospitals, schools, offices, shopping centers
- Industrial facilities: production plants, power plants, refineries
- Tunnels and underground installations: ensuring safe evacuation and operation of safety systems
- Fire protection systems: powering fire pumps, alarm control panels and emergency lighting
Why choose FLAME-X 950?
- Fire resistance: Maintains circuit continuity for at least 180 minutes at 750°C (IEC 60331-21).
- Halogen-free: Minimizes the emission of toxic gases during combustion (according to IEC 60754).
- Low smoke emission: Provides better visibility during evacuation (according to IEC 61034-2).
- Wide temperature range: From -40°C to +90°C – guarantees reliability in various environmental conditions.
- Compliance with standards: Meets stringent European and Polish standards regarding fire safety.
- Mechanical strength: Solid construction provides resistance to damage during installation and operation.
- Conductor resistance: for a cross-section of 6 mm² is 3.08 Ohm/km, which translates to efficient energy transmission.
CERTIFICATES, APPROVALS, SAFETY, COMPLIANCE AND WARNINGS
Information about websites