Reducer RDPP300/200H60N 468630
- 5900993242881
Suggested products
TECHNICAL DATA
Sales unit dimensions and weight: 1 pcs
Reducer RDPP300/200H60N 468630
Cable Route Reduction – Robust and Safe
This reduction, manufactured from steel, is designed to change the width of a cable route. It is a critical component in cable installation systems, enabling flexible adaptation to changing conditions and requirements. The use of high-quality materials ensures durability and structural reliability.
Design and Installation
The RDPP300/200H60N reduction features dimensions of 300 mm (wider side) and 200 mm (narrower side). Constructed from 1.5 mm thick sheet steel, it provides adequate mechanical strength. Installation requires LDCH… connectors and SGKM8x14 or SGM8x14 screws (4 connectors and 16 screw sets needed). For non-standard orders, dimensions 'a' and 'b' must be specified. The design allows mounting of cable supports UK/UKO… and UKP….
Safety and Compliance with Standards
This reduction meets the E-90 fire resistance rating, ensuring at least 90 minutes of operational integrity for critical building systems during a fire. This is especially vital for fire alarm systems, fire detection, and emergency lighting. Surface protection via hot-dip galvanizing further enhances corrosion resistance and ensures long-term protection.
Available in multiple material variants:
- S – Steel coated by Sendzimir process (PN-EN 10346:2015-09) – standard version.
- F – Steel hot-dip galvanized (PN-EN ISO 1461:2023-02) – available on request; offers superior corrosion resistance.
- E – Stainless steel – available on request; ideal for aggressive environments.
- L – Powder coating in standard RAL color palette – available on request; allows color matching to surroundings.
The E90 fire integrity system (per DIN 4102-12) guarantees continuous operation of critical safety systems during a fire. This is not merely a structural component—it is a vital element ensuring the safety of people and property.
CERTIFICATES, APPROVALS, SAFETY, COMPLIANCE AND WARNINGS
Declaration of Conformity
- Deklaracja-Zgodnosci-UE-nr-1_23-CE-standard-PN-EN.-PL trasy kablowe
- Baks Deklaracja-Zgodnosci-UE-nr-1_25-CE-standard-PN-EN.-PL-17.02.2025
- Deklaracja-Zgodności-CE-2_2016-standard
Information about websites
Other
- Baks Krajowa Ocena techniczna KOT_2023_0371-3703-w2-1 konstrukcje nośne
- Baks Krajowy certyfikat stałosci właściwości uzytkowych 2023 konstrukcje nośne
The declaration of performance
- Baks Krajowy-certyfikat-stalości-wlasciwości-użytkowych -puszki
- Deklaracja-właściwości-użytkowej-konstrukcje-2017-E901 E-90
- Deklaracja-właściwości-użytkowej-zespoły-2017-E90 Baks
Attachments
- 22063_AI_RDPC_H_N
- Warunki gwarancji BAKS
- Baks - Powłoki antykorozyjne
- Baks powłoki antykorozyjne BAKS 2024
- Baks_Informacja o materiałach i powłokach ochronnych materiałów z których wykonane są wyroby B
- BAKS-GPSR-20241210 bezpieczeństwo produktów
- Warunki gwarancji 2020