Fuse disconnect switch 630A, size 3, 3-pole mounting on Sasy 60i, FCL version with box terminals XNH3-FCL-S630-BT 183080
Suggested products
TECHNICAL DATA
Sales unit dimensions and weight: 1 pcs
Fuse disconnect switch 630A, size 3, 3-pole mounting on Sasy 60i, FCL version with box terminals XNH3-FCL-S630-BT 183080
Fuse disconnect switch – reliable installation protection
This three-pole fuse disconnect switch, designed to work with NH3 fuse links, is a key element in protecting the electrical installation. Designed for mounting on 60i rails, it offers solid and safe operation in systems with a voltage of up to 690V AC. The FCL version with box terminals provides convenient and secure connection of wires.
Design and application
This disconnect switch is ideal for use in electrical switchboards, providing effective protection against overloads and short circuits. Its design allows for quick and easy installation, and the ability to connect wires from both the top and bottom increases installation flexibility. The built-in fuse link status control with LED indication allows for quick identification of blown fuses, minimizing system downtime. Short-circuit strength at 120kA (at 500V) or 100kA (at 690V) guarantees reliable operation even in extreme conditions.
Key features and benefits
- High short-circuit strength: Ensures installation safety even with high short-circuit currents.
- Blown fuse indication: Fuse link status control with LED simplifies quick diagnostics and repair.
- Installation flexibility: The ability to connect wires from the top or bottom facilitates installation in various configurations.
- Box terminals: Provide secure and convenient wire connection.
- For NH3 fuse links: Compatibility with popular NH3 fuse links.
- Mounting on 60i rails: Standard mounting simplifies integration with existing distribution systems.
- Solid construction: Made of high-quality materials, guarantees long-lasting and reliable operation.
- Rated continuous current 630A: Allows protection of circuits with high load.
- Rated short-time withstand current Icw 3kA: Provides resistance to transient overvoltages.
This disconnect switch is not only a protective element, but also a practical solution for installers who value ease of installation and reliable operation. For end users, this means peace of mind and confidence that their installation is protected against failures.