High-temperature resistant silicone cable H05SS-F 5G1.5 mm² black, conductor identification according to DIN VDE 0293-308 22301
Suggested products
TECHNICAL DATA
Sales unit dimensions and weight: 1 m
High-temperature resistant silicone cable H05SS-F 5G1.5 mm² black, conductor identification according to DIN VDE 0293-308 22301
Flexible cable H05SS-F – resistance to extreme temperatures
This 5-core H05SS-F cable with a cross-section of 1.5 mm² is a reliable solution for applications requiring high thermal resistance. The cable is designed to operate in a wide temperature range, from -60°C to +180°C (short-term up to +250°C), making it an ideal choice for harsh industrial conditions and specialized installations. A rated voltage of 500V ensures safety and compatibility with most standard electrical installations.
Construction and application
The cable is characterized by a solid construction with stranded copper cores, insulated with crosslinked rubber (SiR) EI2. The outer jacket made of crosslinked rubber EM9 provides additional protection against external factors. The cable is particularly recommended for internal wiring of lighting fixtures in industrial plants and wherever there is contact with high temperatures or hot surfaces. Thanks to the flexibility of class 5 cores, the cable is easy to install and route, even in tight spaces.
Key features and benefits
- Exceptional thermal resistance: Operation at temperatures up to +180°C (short-term +250°C) guarantees reliability in demanding conditions.
- Flexibility: Multi-wire core construction makes it easy to install and route the cable, minimizing the risk of mechanical damage.
- Safety: Rated voltage of 500V ensures safe operation in standard electrical installations.
- Durability: Made of high-quality materials guarantees long life and resistance to external factors.
- Radiation resistance: Up to 20x10⁶ cJ/kg (up to 20 Mrad) – possibility of use in environments exposed to radiation.
- Compliance with standards: Meets the requirements of DIN VDE 0285-525-2-83 / DIN EN 50525-2-83 and the Low Voltage Directive 2014/35/EU (CE marking).
- Minimum bending radius: Flexible 7.5x cable diameter, for fixed laying 4x cable diameter – facilitates installation in tight spaces.
- Core identification: Color-coded cores facilitate correct connection and ensure safe use. Yellow-green protective conductor (in cables with more than 3 cores).