Automatic fire button OP1 flush-mounted 2 NC 1 NO + LED indicator 230VAC + hammer OP1-W02-A\21-230-m OP1-W02-A\21-230-M
Suggested products
TECHNICAL DATA
Sales unit dimensions and weight: 1 pcs
Automatic fire button OP1 flush-mounted 2 NC 1 NO + LED indicator 230VAC + hammer OP1-W02-A\21-230-m OP1-W02-A\21-230-M
Fire alarm manual call point – quick reaction in emergency situations.
This flush-mounted fire call point OP1 is a key element of the fire alarm system, designed for installation inside buildings. Its purpose is to enable manual activation of the alarm in the event of a fire, allowing for rapid evacuation and summoning of emergency services. This model combines reliable operation with a discreet design, perfectly blending into the architecture of modern interiors.
Construction and functionality
The OP1-W02-A\21-230-M call point is a flush-mounted device made of durable plastic in red. It is equipped with two independent changeover contacts (2 CO) and one normally open contact (1 NO), providing flexibility in configuration depending on the installation requirements. Additionally, it has a built-in LED powered by 230VAC, which indicates alarm activation, providing visual confirmation of the activation of safety procedures. The set includes a hammer for replacing the glass.
The operation of the call point depends on type A or B (type A in this model): after breaking the glass, the button is released automatically, making it easy to operate even in stressful situations. The IP65 protection rating guarantees resistance to dust and moisture, allowing installation in various environmental conditions.
Application and compliance with standards
Designed for use in both industrial and public buildings – offices, schools, hospitals or commercial facilities. It meets the requirements of PN-EN 54-11, confirming its compliance with European fire safety standards. It has a certificate of approval No. 2266/2014 and an EC certificate of conformity No. 1438/CPD/0130.
- Quick reaction: Enables immediate activation of the fire alarm.
- High reliability: Made of durable materials, resistant to mechanical damage and atmospheric factors (IP65).
- Visual indication: Built-in LED informs about alarm activation.
- Installation flexibility: Two changeover contacts and one normally open contact allow adaptation to different alarm system configurations.
- Compliance with standards: Meets the requirements of PN-EN 54-11, guaranteeing safety of use.
- Easy operation: Automatic release of the button after breaking the glass makes it easy to use in emergency situations.
Example electrical parameters: continuous rated current 10A and rated switching current AC-15: 2.5A (at 230V) and DC-13: 4A (at 24V). Connection cables should have a cross-section of 1 to 2.5 mm² for solid wires or 0.75 to 1.5 mm² for stranded wires.
CERTIFICATES, APPROVALS, SAFETY, COMPLIANCE AND WARNINGS
Attachments