Manual fire alarm call point OP1 flush-mounted 2 circuits + signaling LED 230VAC OP1-W02-B\02-230
Suggested products
TECHNICAL DATA
Sales unit dimensions and weight: 1 pcs
Manual fire alarm call point OP1 flush-mounted 2 circuits + signaling LED 230VAC OP1-W02-B\02-230
Manual fire alarm – reliable hazard signaling
This flush-mounted device, i.e. manual fire alarm button OP1, is a key element of the fire alarm system. Designed for installation inside industrial and public buildings, it allows for manual activation of the alarm in case of a detected hazard. Made of durable plastic in red color, it is characterized by high resistance to environmental conditions – this is confirmed by the IP65 protection class.
Construction and operating principle
The OP1-W02-B\02-230 is a flush-mounted model with two developments (2 dev.), equipped with an LED indicating the alarm status powered by 230VAC voltage. It should be remembered that this model represents type B according to PN-EN 54-11 – which means that after breaking the protective glass, it is necessary to additionally press the button to activate the alarm. The glass is a replaceable element, and its damage requires replacement with a new one (order symbol PPOŻ-5701), which ensures the continuous readiness of the device to operate.
Application and compliance with standards
The device meets the requirements of the PN-EN 54-11 standard and has appropriate certificates – Approval Certificate No. 2266/2014 and EC Certificate of Conformity No. 1438/CPD/0130. It can be used in various facilities where reliable fire signaling is required. This button offers the possibility of configuring electrical circuits (NO/NC and mixed NC/NO) depending on the needs of a specific installation. For example, NO circuits open after breaking the glass or removing the cover (in the case of type B – after pressing the button), and NC circuits close in the same situations.
Additional information:
- Durable housing: Made of plastic, it provides mechanical resistance and long-term operation.
- LED signaling: Built-in LED facilitates visual identification of the alarm status.
- Easy installation: Designed for flush mounting ensures an aesthetic appearance of the installation.
- Compliance with regulations: Meeting the PN-EN 54-11 standard guarantees safety and reliability.
- Versatility: The possibility of configuring electrical circuits allows adaptation to different alarm systems.
CERTIFICATES, APPROVALS, SAFETY, COMPLIANCE AND WARNINGS