Overcurrent circuit breaker ETIMAT 10 3p C80 002135731
Suggested products
TECHNICAL DATA
Sales unit dimensions and weight: 1 pcs
Overcurrent circuit breaker ETIMAT 10 3p C80 002135731
Overcurrent circuit breakers ETIMAT 10 are reliable and proven devices designed to protect electrical installations in residential, public and industrial buildings. They provide effective protection against the effects of short circuits and overloads, guaranteeing safe operation. The design of the circuit breakers allows for mounting on a TH35 rail, which facilitates installation and replacement.
Functionality and application
ETIMAT 10 circuit breakers are characterized by versatility and the ability to adapt to different needs. A rated current of 80A combined with characteristic C makes them ideal for circuits with devices with high starting current - e.g. motors. The rated short-circuit breaking capacity Icu is 20kA at 400V, which ensures high effectiveness in the event of a failure. The possibility of powering from the bottom and from the top, as well as double connection (busbar and wire) increase flexibility during installation.
User comfort and additional functions
ETIMAT 10 circuit breakers have been designed with the convenience of installers and end-users in mind. The ability to seal the lever in the "On" and "Off" positions prevents accidental change of the circuit breaker state, and the contact position indicator facilitates quick identification of the circuit state. Additionally, the possibility of mounting auxiliary contacts and overcurrent and undervoltage releases allows for expanding the functionality of the circuit breaker and adapting it to specific installation requirements. Each circuit breaker is marked with a unique EAN code for easy identification and inventory management.
- The width of the device is 4.5 modules, which allows for efficient use of space in the switchgear.
- The degree of protection IP20 provides protection against accidental contact.
- The ambient temperature in operating conditions is in the range of -25°C to +55°C, which allows the use of circuit breakers in various environmental conditions.
- Compliance with IEC/EN 60898-1 and IEC 60947-2 standards guarantees safety and reliability of operation.
- The cross-section of the connected single-wire or multi-wire conductor is from 2.5 mm² to 50 mm², which ensures compatibility with various types of conductors.
- The rated insulation voltage Ui is 440V and the rated impulse withstand voltage Uimp is 4kV providing a high level of insulation safety.
CERTIFICATES, APPROVALS, SAFETY, COMPLIANCE AND WARNINGS
cert_title_deklaracja_zgodności_(ce)