Overcurrent circuit breaker ETIMAT 6 1P+N B13 002112515
Suggested products
TECHNICAL DATA
Sales unit dimensions and weight: 1 pcs
Overcurrent circuit breaker ETIMAT 6 1P+N B13 002112515
Reliable protection of electrical installations – ETIMAT 6 circuit breaker
ETIMAT 6 circuit breaker is a proven element of protection in electrical installations. It will work in residential buildings, public and industrial facilities. It provides effective protection against the effects of short circuits and overloads, protecting electrical circuits and devices connected to them. The 1P+N design with B characteristic makes it ideal for protecting lighting and socket circuits.
Functionality and technical parameters
This two-pole (1P+N) circuit breaker with a rated current of 13A is designed to operate in networks with a voltage of 400V. The rated short-circuit breaking capacity of 6kA at 230V and 400V guarantees a quick response in the event of a failure. The B characteristic ensures that the circuit breaker will react quickly to short-term overloads, but will allow the starting of motors without unnecessary tripping. The degree of protection IP20 means that it is protected against touching with a finger and the ingress of solid objects larger than 12.5 mm.
- Modular width: 2 modules – compact dimensions make it easy to mount in switchboards.
- Wire cross-section: Possibility of connecting solid and stranded wires with a cross-section from 1 to 25 mm², which gives flexibility in choosing wires.
- Operating temperature: Wide operating temperature range from -25°C to +55°C allows the circuit breaker to be used in various environmental conditions.
- Compliance with standards: Meets the requirements of IEC/EN 60898-1 and IEC 60947-2 standards, which confirms its safety and reliability.
- Impulse voltage: Withstands impulse voltage up to 4kV, which increases resistance to overvoltage.
Installation and additional functions
ETIMAT 6 circuit breaker offers convenient mounting on a TH35 rail and the possibility of connecting wires from both the top and the bottom. In addition, it is possible to mount auxiliary contacts (PS ETIMAT 10) and an overcurrent release (DA ETIMAT 10), which expands the functionality of the device. The contact position indicator and the possibility of sealing the lever provide additional safety and control over the state of the circuit breaker. Each unit is marked with a unique EAN code for easy identification.
CERTIFICATES, APPROVALS, SAFETY, COMPLIANCE AND WARNINGS
cert_title_deklaracja_zgodności_(ce)
Certificate of Conformity