Stationary circuit breaker with Sentinel trip unit, 66 kA, 1250 A, 3‑pole HW1E312FB

from 1 pcs12 874,46 zł
gross / pcs
to order
Brand HAGER
Series:ACB HW1
Onninen Index:CVF628
Manufacturer's code:HW1E312FB
EAN:3250613235765
Bulk packaging:1 pcs


Suggested products


TECHNICAL DATA

Sales unit dimensions and weight: 1 pcs

length/width/height/weight/volume:0,2 m / 0,276 m / 0,313 m / 44 kg / 0,017 m3
Customs code:85362090

Stationary circuit breaker with Sentinel trip unit, 66 kA, 1250 A, 3‑pole HW1E312FB

Stationary circuit breaker with Sentinel trip unit – 1250 A, 66 kA, 3P

This device is designed for permanent installation in low‑voltage switchgear, where high breaking capacity and reliability in industrial conditions are required. Rated continuous current 1250 A and short‑circuit rating 66 kA at 400 V allow safe handling of large loads – e.g., in installations with motors, transformers or systems with high inrush current.

The built‑in Sentinel trip unit provides selective overload and short‑circuit protection, and its configuration is adapted to installation requirements without the need for additional modules. The device does not have an integrated earth‑fault protection – if such protection is required, it must be implemented externally.

Main connections are designed for busbar connections, eliminating the need to mount cables directly to terminals – this facilitates integration with switchgear busbars and reduces installation time. Installation is not performed on a DIN rail; the device is permanently mounted to the switchgear frame, ensuring stability even under high electrodynamic forces.

A benefit is the trip indicator – it allows quick visual diagnosis of the device’s status without opening the enclosure. This is especially useful during inspections or faults when response time matters.

Four auxiliary changeover contacts (neither make‑nor‑break) enable integration with control and signaling systems – e.g., to indicate “on”/“off” status or trigger alarms. However, there is no built‑in motor drive – it can be supplied as an external option, providing flexibility for upgrades.

The IP2X protection rating guarantees protection against contact with live parts, but does not provide dust or water protection – therefore the device should be installed in enclosures with an appropriate IP class.

The rated voltage range of 440 to 690 V makes it suitable for both 400 V systems and industrial installations with higher phase voltage (e.g., 575 V). There is no under‑voltage trip function – if voltage dip protection is needed, it must be added externally.

The package does not include protection – this device itself serves as the main circuit breaker and requires appropriate protective modules to be matched (if needed).


CERTIFICATES, APPROVALS, SAFETY, COMPLIANCE AND WARNINGS

cert_title_certyfikat_pep_(certyfikat_profilu_ekologicznego_produktu)[eko_label]

Deklaracja zgodności WE



SIMILAR PRODUCTS / OTHER SIZES


from 1 pcs12 874,46 zł
gross / pcs
to order