Fire-resistant power cable (N)HXH-J FE180/E90 5x4 1kV G-144923
reviews: 6
Suggested products
TECHNICAL DATA
Sales unit dimensions and weight: 1 m
Fire-resistant power cable (N)HXH-J FE180/E90 5x4 1kV G-144923
Fire-resistant power cable – safety and reliability in critical situations
This 5-core power cable (N)HXH-J FE180/E90 with a cross-section of 4 mm² is designed for installations requiring continuous power supply in fire conditions. It meets the E90 standard, which means it will maintain its function for 90 minutes even under high temperature. This is crucial in facilities with increased fire protection requirements, such as hospitals, shopping centers, skyscrapers or tunnels. This cable is ideal for powering and controlling devices such as emergency lighting, fire protection systems or elevators.
Construction and properties
The cable is made of copper conductors of class 1 (solid core), insulated with a material meeting the requirements of halogen-free (according to IEC 60754-1 and IEC 60754-2). The outer sheath made of polyolefin provides resistance to mechanical damage and atmospheric factors. The lack of a screen and armor makes the cable flexible and easy to install. It is worth noting its resistance to UV radiation, which allows it to be used in outdoor installations as well (but not directly in the ground or water). Thanks to low smoke emission (according to IEC 61034-2) and the absence of halogen, the cable minimizes the risk of toxic gases forming during a fire.
Application and benefits
The (N)HXH-J FE180/E90 cable is used in dry and damp rooms, both indoors and outdoors (with reservations regarding direct contact with the ground or water). Its fire resistance guarantees the continued operation of critical systems during a fire, which can save lives and reduce material losses. Color-coded core identification makes installation simple and intuitive. The use of copper as a conductive material ensures good electrical conductivity and long-term reliability. This cable complies with DIN VDE 0266, which confirms its high quality and safety of use. The approximate outer diameter of the cable is 16.9 mm and its weight is 493.387 kg/km. The minimum bending radius during permanent installation is 202.8 mm.
CERTIFICATES, APPROVALS, SAFETY, COMPLIANCE AND WARNINGS
Declaration of Conformity
- TELEFONIKA-Deklaracja zgodnosci UE TF3 0138.1 (2020-02-24)
- TECHNOKABEL - 214_19 NHXH-J, NHXCH. (N)HXH-J, (N)HXCH_06_1 kV
- ELPAR - deklaracja NHXH 37.17
- EUPEN_Deklaracja zgodności NHXH E90_PL
- tf_deklaracje_nhxh_0,6
Information about websites
The declaration of performance
- TELEFONIKA-KDWU-18-0001-02 (N)HXH; (N)HXCH
- TECHNOKABEL - KDWU-17-00192-02
- ELPAR - KDWU NHXH, NHXCH, (N)HXH, (N)HXCH nr 0003-18
Attachments
- TECHNOKABEL - K273P1901_(N)HXH FE180 PH90_E90
- ELPAR - (N)HXH-J v2 (1)
- TELEFONIKA-FLAME-X_950_(N)HXH_FE180-E90_PL_MK-14-01-2020