Interface relay 2P, AgNi, 24 V DC PI72P-024DC-Y42G-US-2012 2617330
Suggested products
TECHNICAL DATA
Sales unit dimensions and weight: 1 pcs
Interface relay 2P, AgNi, 24 V DC PI72P-024DC-Y42G-US-2012 2617330
Complete interface kit for professional applications
This interface relay is a ready-to-use solution for installers and end-users seeking a reliable switching component in automation systems. The kit includes all necessary components: the electromagnetic relay RMP7 with two pairs of silver-nickel alloy (AgNi) contacts, the GZP72 socket, and the Y42G signaling and surge protection module.
Construction and technical parameters
The relay operates at a control voltage of 24 V DC in monostable mode with polarized drive. The housing dimensions of 80.4 × 15.7 × 66.1 mm enable compact installation on a standard DIN 35 mm rail according to PN-EN 60715 or directly on a mounting plate using a single M3 screw. The device weighs only 59.7 g, facilitating installation even in hard-to-reach locations.
The protection class IP20 prevents finger contact and access to hazardous parts. Contacts made of silver-nickel alloy (AgNi) ensure a minimum switching voltage of 12 V and a continuous current rating of up to 8 A. The minimum switching power is 1 W, allowing operation even under very low loads.
Functionality and signaling
The device features a multifunctional status signaling system. A red LED indicates AC power supply, while a green LED indicates DC power supply - this practical solution enables quick identification of the power supply type without consulting technical documentation.
A mechanical actuation indicator allows immediate verification of contact status without disassembling the device. Additionally, a test button located on the front of the device enables functional testing and includes a contact locking function - particularly useful during maintenance or servicing.
Installation and electrical connections
The push-in system significantly simplifies the installation process - wires can be connected tool-free by inserting the conductor into the appropriate opening. The maximum wire cross-section is 2 × 1.5 mm² (without insulated ferrules) or 2 × 1 mm² (with insulated ferrules). The wire stripping length should be 8-10 mm to ensure optimal electrical contact.
The operating range of the supply voltage is 0.8...1.1 U, and the dropout voltage for AC is ≥0.3 U - these parameters guarantee stable operation under varying network load conditions.
The product meets European standard requirements and is covered by full technical documentation from RELPOL.
CERTIFICATES, APPROVALS, SAFETY, COMPLIANCE AND WARNINGS
cert_title_deklaracja_zgodności_(ce)
Attachments