Overcurrent circuit breaker, 6kA, B characteristic, 1-pole, 16A MBN116E
reviews: 10
Suggested products
TECHNICAL DATA
Sales unit dimensions and weight: 1 pcs
Overcurrent circuit breaker, 6kA, B characteristic, 1-pole, 16A MBN116E
Safety and reliability in your electrical installation
Hager MBN116E circuit breaker is a key element of every modern electrical installation, providing effective protection against the effects of overloads and short circuits. The device is characterized by fast operation, high reliability and simple installation, making it an ideal choice for both professionals and home users. Thanks to its compact size and the possibility of mounting on a DIN rail, the breaker easily integrates with the existing electrical infrastructure.
Key features and benefits
Protection against overloads and short circuits: The breaker automatically cuts off the power in the event of a dangerous increase in current, protecting wires, devices and people from damage.
B characteristic: Provides a quick response to short-term current surges, which is particularly important in circuits with devices with high starting power consumption (e.g. motors).
Rated breaking capacity 6kA: Guarantees safe interruption of the circuit even with high short-circuit currents.
Universal application: Suitable for protecting lighting circuits, socket outlets and other loads in residential and commercial buildings.
Easy installation: Compact dimensions and the possibility of mounting on a standard 35 mm DIN rail facilitate installation.
Durable construction: Made of high-quality materials, ensuring long life and reliable operation.
Wide voltage range: Designed to operate in installations with a voltage of 230/400 V AC.
The MBN116E breaker is characterized by a rated current of 16 A and a tripping characteristic of B. Its rated breaking capacity is 6 kA (at 230 V), and the number of poles is 1P (single-pole). It is designed to operate at a rated voltage of 230/400 V AC and a frequency of 50/60 Hz. The width of the breaker is 1 module (17.5 mm), it has a protection degree of IP20 and a working temperature range from -25°C to +70°C.
This breaker complies with the PN-EN 60898-1 standard, which confirms its safety and quality. It also has energy limitation class 3 and pollution degree 2. The cross-section of the connected solid wire is from 1 to 35 mm², and the stranded wire from 1 to 25 mm².
Application
Hager MBN116E circuit breaker finds wide application in various types of electrical installations:
Home installations (protection of lighting circuits, sockets)
Commercial installations (offices, shops)
Industrial installations (applications with lower power consumption)
Electrical switchboards
Thanks to its reliability and versatility, this breaker is an excellent choice for anyone who cares about the safety of their electrical installation.
CERTIFICATES, APPROVALS, SAFETY, COMPLIANCE AND WARNINGS
Declaration of Conformity
Deklaracja zgodności WE
Information about websites
Attachments