Residual current circuit breaker with overcurrent protection B/6kA, 16A, 30mA, 2-pole, type A ADA916D

5/5

reviews: 1

Variants
from 1 pcs293,07 zł
gross / pcs
z 104 pcs
z 104 pcs
Brand HAGER
Onninen Index:HDD741
Manufacturer's code:

Catalog numbers:

  • AD916J
EAN:
  • 3250611010647
Bulk packaging:1 / 60 pcs

Variants


Suggested products


TECHNICAL DATA

Sales unit dimensions and weight: 1 pcs

length/width/height/weight:0,07 m / 0,035 m / 0,094 m / 0,224 kg
Customs code:85363010

Residual current circuit breaker with overcurrent protection B/6kA, 16A, 30mA, 2-pole, type A ADA916D

Residual Current Circuit Breaker with Overcurrent (RCBO) is a reliable protection for electrical installations, combining the functions of an overcurrent and residual current circuit breaker. Model ADA916D, with a rated current of 16A and a sensitivity of 30mA, provides comprehensive protection against the effects of short circuits, overloads, and electric shock. The two-pole design (1P+N) makes it ideal for protecting lighting, socket, and other circuits in residential and commercial buildings.

Characteristics and application

The circuit breaker is characterized by a B tripping characteristic, which means it reacts quickly to an increase in short-circuit current, but is more tolerant to short-term inrush currents – which is particularly important when connecting devices with induction motors or other pulsed loads. Type A indicates its ability to detect alternating residual currents, providing protection for people against electric shock. The rated short-circuit breaking capacity Icn of 6kA guarantees effective disconnection of the circuit in the event of a serious failure.

Advantages and benefits

  • Versatile protection: Combining overcurrent and residual current protection in one device simplifies installation and increases safety.
  • Fast response: Characteristic B ensures quick tripping in the event of short circuits, minimizing the risk of damage to the installation and equipment.
  • Protection against electric shock: 30mA sensitivity effectively detects leakage currents, protecting users from dangerous electric shocks.
  • Easy installation: 2 module width allows for easy installation in standard distribution boards. Flush mounting option further increases flexibility.
  • Safety of use: Protection against contact IP2X and a lock preventing accidental opening of the device ensure a high level of safety during operation.
  • Durable construction: Made of high-quality materials, guarantees reliable operation for a long time.
  • Wide operating temperature range: Allows operation in difficult environmental conditions (-25°C to +40°C).
  • Compatibility with DIN rails: Facilitates integration with existing distribution systems.

Design and parameters

The circuit breaker is designed for ease of installation and maintenance. It has screw terminals allowing the connection of wires with a cross-section from 1 mm² to 25 mm² (solid) and from 1 mm² to 16 mm² (stranded). The rated insulation voltage Ui is 500V, and the rated impulse withstand voltage Uimp is 4kV – confirming its resistance to overvoltages. The energy limitation class is 3, which indicates high efficiency in suppressing short-circuit energy. Additionally, the circuit breaker has two contact position indicators and a residual current release facilitating fault diagnosis.

Innovative vertical comb rails - A quick, easy and safe way to connect selected devices in 2- or 3-rows of the switchgear
Description field with a protective flap - Clear and aesthetic marking of apparatus is now even easier thanks to the printouts from the Semiolog program and a transparent protective flap.
Safety and protection against errors - Protection against contact with IP2x, also with the use of phase busbars. Elimination of errors when inserting the wire into the terminal thanks to protective caps.
2 position indicators: contacts and residual current trip - Complete and unambiguous definition of the cause of the RCD tripped (especially important in fault diagnostics).
Comprehensive offer - Devices available in the range of rated currents from 0.5 to 125 A, in

CERTIFICATES, APPROVALS, SAFETY, COMPLIANCE AND WARNINGS

Declaration of Conformity

Information about websites

Product ecological profile certificate

Attachments



CUSTOMER OPINIONS ABOUT THE PRODUCT (1)

0/5
No reviews to display.

SIMILAR PRODUCTS / OTHER SIZES


from 1 pcs293,07 zł
gross / pcs
z 104 pcs
z 104 pcs