PVC/LS0H cable for submersible pumps for drinking water HELUPOWER® AQUATIC-750-BLUE 4G6 mm² blue, core identification acc. to DIN VDE 0293-308 11018155
Suggested products
TECHNICAL DATA
Sales unit dimensions and weight: 1 m
PVC/LS0H cable for submersible pumps for drinking water HELUPOWER® AQUATIC-750-BLUE 4G6 mm² blue, core identification acc. to DIN VDE 0293-308 11018155
Submersible pump cable – reliable power in harsh conditions
This blue HELUPOWER® AQUATIC-750-BLUE cable is a specialized solution for powering submersible pumps, designed for operation in demanding aquatic environments. This cable, with a cross-section of 6 mm² and a 4G construction, is perfect for both home installations and professional water supply systems. Its construction and materials guarantee safety and long-lasting reliability.
Construction and application – the key to durability
The cable is manufactured in accordance with DIN VDE 0250/DIN VDE 0285-525-1/DIN EN 50525-1 standards, which demonstrates its high quality and compliance with European standards. It can be used as a connection cable in food processing plants, fish ponds, aquariums, and of course for powering submersible pump motors immersed to a depth of up to 600 meters. Un-tinned, stranded copper conductors, class 5, provide flexibility and resistance to mechanical damage. The core insulation is made of PVC, and the color identification complies with DIN VDE 0293-308, making correct installation easier.
- Versatile application: ideal for submersible pumps, sensors, drive motors and underwater heating systems.
- Resistance to external factors: designed for use in drinking and salt water (up to 3.5% salinity), resistant to chlorine (up to 0.6 mg/l).
- Safety: has a PZH certificate allowing contact with drinking water, and no growth of microorganisms or emission of toxic substances.
- Durability: cross-linked halogen-free plastic coating provides mechanical and chemical resistance.
- Flexibility: construction with stranded copper conductors class 5 facilitates installation and cable routing.
User and construction parameters
The cable is characterized by a working voltage of 0.6/1kV and an operating temperature of -40°C to +80°C (stationary) and -25°C to +50°C (flexible). The minimum bending radius is 5x the cable diameter, making it easy to lay even in tight spaces. The outer coating is made of cross-linked polymer in blue RAL 5015. The cable has a yellow-green protective conductor for increased safety. The weight of one meter of cable is approximately 0.377 kg and the outer diameter is approximately 15 mm. The cable construction is 4G6 – four cores with a cross-section of 6 mm².
CERTIFICATES, APPROVALS, SAFETY, COMPLIANCE AND WARNINGS
cert_title_deklaracja_zgodności_(ce)
Attachments